phone line fault, phone off hook, alarm input line status (Normal, Fault with alarm trip
delay not timed out, Unacknowledged Alarm, and Acknowledged Alarm).
1.3
Power, Operational Backup Battery, and User Program Storage
Main power for the dialer shall be either 10-14 VDC or 105-135 VAC. The latter requires the
GAC option.
Backup power to allow dialer operation should main power be lost shall be by an internal 6 V, 4
AH gel cell rechargeable battery and precision voltage controlled charger, option GBB. A trickle
charger shall not be supplied. Battery backup shall be 20 hours.
User program storage shall be by an internal lithium battery rated for 10 years from date of
shipment. Dialer operating system and default voice messages shall be stored in non-volatile
memory.
1.4
Surge protection
Unit shall have solid state surge protection on phone, power, and signal lines. Surge protection
modules shall be replaceable at the RACO Factory.
1.5
Warranty, Repairs, Technical Support
The unit shall be covered by a Two (2) Year Warranty covering parts and labor performed at the
Factory.
RACO Factory repairs shall be available. No-cost loaners shall be available prior to shipping
defective dialers to the Factory.
RACO Factory technical support shall be provided to assist in programming, diagnosis, and
product information. Support shall be by:
a. Toll Free 800 Number --- during RACO’s normal working day to permit users to talk
directly with technical service personnel.
b.
www.racoman.com --- all literature, manuals, and support access available online.
1.6
UL Standard
Complies with UL Standards 1459, 1950.
1.7
Special Options
The following options shall be available on specific order:
a. Cellular wireless telephone communications.
b. NEMA-4X (sealed) enclosure.