Wiring Connections
Guard-It
TM
Owner's Manual 3-1
3 Wiring Connections
!
Note:
Note that the connector block is unpluggable for convenience in making
wiring connections.
3.1 Power Connections
The Guard-It
TM
autodialer requires 8 to 16 VDC power connected to the
connector block, in order to operate.
The power source should be capable of delivering a current of 500
milliamperes.
Power must be connected observing the correct polarity. Refer to the diagram.
3.2 Connecting To Electrical Ground
Your Guard-It
TM
autodialer has several internal protective devices built in.
However, for them to work effectively it is important that the product be well
grounded. A grounding wire with a terminal lug is included on the product for
this purpose.
If the Product is mounted to a grounded metal back surface, then simply
connect the terminal end of the wire to the lower right hand mounting screw as
shown in the diagram.
If the product is not mounted to a grounded metal back surface, connect the end
of the wire to the nearest available electrical grounding point. If the installation
is within a grounded metal electrical panel or enclosure, connecting to the
metalwork will be sufficient. If you need to extend the ground wire, use 18
gauge wire or heavier, and keep the total length as short as possible.
This grounding wire will also ground the (-) side of the incoming 12 VDC
power. If you are using a pre-existing source of 12 VDC power, you will need
to verify that the grounding of the (-) side of this supply will not cause a
problem.